NE200
0.4KW - 900KW
0 - 550Hz
NE Drive Highlights
✓
Simple, Reliable, Easy
✓ Outstanding control
performance
✓ Superior
Adaptability
✓ Optimize EMC design,
immunity for high interference environment
✓ Compact design,
based on thermal simulation & design to reduce product size
✓ Excellent
Price/Performance Ratio
- Input
Rated power/ frequency |
NE200-2Sxxxx: 1-phase 200V ~
240V; 50Hz/60Hz |
Voltage range |
NE200-2Sxxxx: 176V ~ 264V; Voltage unbalance degree: < 3%
; permissible frequency fluctuation: ±5% |
- Output
Voltage range |
NE200-2Sxxxx: 0~200V/440V;
NE200-4Txxxx: 0~380V/440V |
Overload capacity |
Type G: 150% rated current 1min, 180% rated current 20s |
- Control features
Control mode |
Vector control with PG(VC) |
Vector control without
PG(SVC) |
V/F control |
Startup torque |
---- |
0.5Hz 150% |
1.5Hz 150% |
Speed adjustable range |
---- |
1:100 |
1:50 |
Speed stabilization precision |
---- |
± 0.2% |
± 0.5% |
Torque control |
---- |
Yes |
N/A |
Torque precision |
---- |
± 10% |
---- |
Torque response time |
---- |
<20ms |
---- |
- Product functions
Key functions |
Torque/speed control mode
switching, Multi-function input/ output terminals, under voltage regulation,
AC operation grounding switching, torque limit, multi step operation, slip
compensation, PID regulation, simple PLC, current control, manual/ automatic
torque boost, current limit, AVR function |
Frequency setup |
Keypad, terminal Up/Down, Communication, Analog input AI1/AI2 |
Output frequency |
0.00~550.0Hz |
Startup frequency |
0.00~60.00Hz |
Acc/Dec time |
0.01~3600.0s |
Dynamic braking |
400V drive: braking unit action voltage: 650 ~ 750V; |
DC injection braking |
DC braking activation
frequency: 0.00 ~ 550.0Hz |
Magnetic flux braking |
Fast deceleration through adding motor magnetic flux |
- Unique functions
Parameter cloning |
Parameter upload, download.
User can forbid the overwriting of the uploaded parameters. |
- Protection function
Power undervoltage/overvoltage
protection, overcurrent protection, IGBT protection, heatsink overheat
protection, drive overload protection, motor overload protection, External
devices faults protection, output phase-to-phase short-circuit protection,
Abnormal power failure in running, power supply trip, output phase loss,
EEPROM trip, Analog input trip, communication trip, version compatibility
trip, cloning trip, hardware overload protection |
- Environment
Application environment |
Vertical installation in well
ventilated cabinet. Horizontal or other installation are forbidden. The
cooling medium is air. Free from direct sunlight, dust, corrosive gas,
combustible gas, oil mist, steam, and water drop. |
Ambient temperature |
-10~+40°C, deration is required from 40 to 50°C, rated output current
decreasing 1% per 1°C temperature higher |
Humidity |
5~95% without condensation |
Altitude |
0~2000m, deration is required for more than 1000 meters, at rated
output current decreasing 1% per 1 00m higher |
Vibration |
3.5mm, 2~9Hz; 10 m/s2, 9~200Hz;
15 m/s2, 200~500Hz |
Storage temperature |
-40~+70°C |